Taking our ID fans overseas

Introduction:

We designed, manufactured and installed the Backward Curved (BC) Industrial fan for a client in Bangladesh in December 2017.The application for which we catered was of steel fabrications.

Thus the dust collected through the induction furnace, there is a necessity for usage of fans to minimize the high operating temperatureand the ID Fan installed helped to curb the emissions from it.

CLAIR has executed a couple of projects in Bangladesh and the enquiry we received by this client stated a requirement of both an APC Main Fan and a RA Fan.

Test Conducted:

The Performance Test was conducted and the results are mentioned below:-

Data/ Table:

Given are the different parameters specified in Table 1 with the installation of ID Fan with our Bangladesh Client.

Table 1: Design parameters of the ID Fan

Sl. No.

Description

Unit

Value

1.

Fan Volume

CMH

6,90,000

2.

Pressure

mmwg

-370/ 280

3.

Gas Temperature

0C

90

4.

Dust Load

gm/ Nm3

10

5.

Efficiency

%

81.6

6.

Fan Speed

RPM

980

7.

Impeller Diameter

mm

Ø 2440

8.

Motor Rating

Kw/ Rpm

1850/ 990

9.

ISO/Grade

 

1940/ 2.5

10.

Shaft MoC

 

EN8 – Forged (UT Tested)

Special Notes:

Clair took up the challenge and following was implemented:

  1. Double Width Double Inlet (DWDI)
  2. Simply Supported
  3. Erosion Protection : Chromium Carbide Liner on Impeller
  4. Bolted type liner for Scroll & Fan Casing
  5. Impeller Cleaning Nozzle by Air

 